고객센터
Customer Center
Customer Center
ATS:620-630CT
Frame |
620CT |
630CT | |||||
Rated Current(In) |
A |
2000 |
2500,3000 | ||||
Rated Voltage(Ue) |
V |
AC600 |
AC600 | ||||
Rated Insulation Voltage(Ui) |
V |
AC800 |
AC800 | ||||
Rated Impulse Voltage(Uimp) |
kV |
8 |
8 | ||||
Pole |
P |
3,4 |
3,4 | ||||
Throw |
T |
Double Throw |
Double Throw | ||||
Connection Type |
Front |
- |
- | ||||
Back |
● |
● | |||||
Performance | |||||||
Short Time Current(1s) lcw |
kA |
40 |
25 | ||||
Short Circuit Peak Current lcm |
kA |
40 |
25 | ||||
With Specific Circuit Breaker |
kA |
85 |
50 | ||||
Fuse Mounting |
kA |
200 |
200 | ||||
Switch Capacity Note1) |
Class |
AC-33B |
AC-33B | ||||
Endurance |
Electrical |
5,000 |
3,000 |
5,000 | |||
Mechanical |
10,000 |
5,000 |
10,000 | ||||
Transfer Sequence |
A↔overlapping↔B, A↔B, A↔Neutral(off)↔B | ||||||
Conduction for Uninterrupted Switchover |
Phase difference : Within electrical angle 10°, Frequency difference : Within 0.2Hz, Voltage : Voltage difference with the commercial one is within 5%, Instantaneous Interconnection Time : Within 0.05 second | ||||||
Operation Time |
Closing |
msec |
≤250 |
≤150 | |||
Trip |
msec |
≤80 |
≤30 | ||||
Conditions of Uninterruptible Transfer |
3P |
4P |
3P |
4P | |||
Closing |
AC/DC 110V |
A |
13 |
16 |
16 |
18 | |
AC 220V |
A |
6.5 |
8 |
8 |
9 | ||
Trip Note2) |
AC/DC 110V |
A |
4 |
4 | |||
AC 220V |
A |
2 |
2 | ||||
Dimensions & Weights | |||||||
Front Size(mm)
|
H |
- |
- |
- |
- | ||
W |
- |
- |
- |
- | |||
D |
- |
- |
- |
- | |||
Back Size(mm) |
H |
580 |
580 |
580 |
580 | ||
W |
685 |
820 |
835 |
1020 | |||
D |
335 |
335 |
370 |
370 | |||
Weight |
Front |
kg |
- |
- |
- |
- | |
Back |
kg |
130 |
150 |
165 |
205 | ||
Additional Product Information | |||||||
Circuit diagram |
A6-24 |
A6-24 | |||||
Drawing |
A6-43 |
A6-43 | |||||
Precautions |
A6-18 |