본문 바로가기 주메뉴 바로가기

고객센터

Customer Center

QR

home > 고객센터 > QR

 

ACB:2000/4000AF

비츠로이엠 2018-03-19 조회수 5,410

○ ACB:2000/4000AF

 

 

Rating (50kA)


Type

VABS16

Economic type

Frame size

(AF)

2000

Rated Current(In)

(A) at 40℃

200

400

630

800

1000

1250

1600

Rated Operating Voltage(Ue)

(V)

690

Rated Insulation Voltage(Ui)

(V)

1000

Rated Impulse Voltage(Uimp)

(kV)

12

Frequency

(Hz)

50/60

Poles

(P)

3,4

Set Current(Iu)

(A) x In

0.5/0.6/0.7/0.8/0.9/1.0

N-phase Rated Current

(%In)

100

Rated Breaking Current(Icu)

kA

IEC60947-2

690V/600V/550V

50

500V/480V/460V

65

415V/380V/220V

65

Rated Service Breaking capacity(lcw)

(%In)

100

Rated Closing Current(lcu)

kA

IEC60947-2

690V/600V/550V

105

500V/480V/460V

143

415V/380V/220V

143

Rated Short Time Current(lcw)

(kA)/1s

50

Operation Time

(ms)

Total Breaking Time(In)

40

Closing Time(In)

80

Service Time

(Times)

Mechanical

Maintained

15,000

Unmaintained

10,000

Electrical

Maintained

10,000

Unmaintained

10,000

Installation Type

Fixing(Vertical)

Fixing(Horizontal)

Fixing(Plane)

Draw-out(Vertical)

Draw-out(Horizontal)

Draw-out(Plane)

Certificated

KS C 4620

-


Rating (65kA)

 

 

Type

VABS20

Standard type

Frame size

(AF)

2000

Rated Current(In)

(A) at 40℃

*1)200

*2)400

630

800

1000

1250

1600

2000

Rated Operating Voltage(Ue)

(V)

690

Rated Insulation Voltage(Ui)

(V)

1000

Rated Impulse Voltage(Uimp)

(kV)

12

Frequency

(Hz)

50/60

Poles

(P)

3,4

Set Current(Iu)

(A) x In

0.5/0.6/0.7/0.8/0.9/1.0

N-phase Rated Current

(%In)

100

Rated Breaking Current(Icu)

kA

IEC60947-2

690V/600V/550V

65

500V/480V/460V

85

415V/380V/220V

85

Rated Service Breaking capacity(lcw)

(%In)

100

Rated Closing Current(lcu)

kA

IEC60947-2

690V/600V/550V

143

500V/480V/460V

187

415V/380V/220V

187

Rated Short Time Current(lcw)

(kA)/1s

50

Operation Time

(ms)

Total Breaking Time(In)

40

Closing Time(In)

80

Service Time

(Times)

Mechanical

Maintained

15,000

Unmaintained

10,000

Electrical

Maintained

10,000

Unmaintained

10,000

Installation Type

Fixing(Vertical)

Fixing(Horizontal)

Fixing(Plane)

Draw-out(Vertical)

Draw-out(Horizontal)

Draw-out(Plane)

Certificated

KS C 4620

 

Type

VABS40

Standard type

Frame size

(AF)

4000

Rated Current(In)

(A) at 40℃

2500

3200

4000

Rated Operating Voltage(Ue)

(V)

690

Rated Insulation Voltage(Ui)

(V)

1000

Rated Impulse Voltage(Uimp)

(kV)

12

Frequency

(Hz)

50/60

Poles

(P)

3,4

Set Current(Iu)

(A) x In

0.5/0.6/0.7/0.8/0.9/1.0

N-phase Rated Current

(%In)

100

Rated Breaking Current(Icu)

kA

IEC60947-2

690V/600V/550V

85

500V/480V/460V

100

415V/380V/220V

100

Rated Service Breaking capacity(lcw)

(%In)

100

Rated Closing Current(lcu)

kA

IEC60947-2

690V/600V/550V

187

500V/480V/460V

220

415V/380V/220V

220

Rated Short Time Current(lcw)

(kA)/1s

65

Operation Time

(ms)

Total Breaking Time(In)

40

Closing Time(In)

80

Service Time

(Times)

Mechanical

Maintained

15,000

Unmaintained

10,000

Electrical

Maintained

10,000

Unmaintained

10,000

Installation Type

Fixing(Vertical)

Fixing(Horizontal)

X

Fixing(Plane)

X

Draw-out(Vertical)

Draw-out(Horizontal)

X

Draw-out(Plane)

X

Certificated